BURNERS IGNITERS   FLAME DETECTORS

FORNEY 火焰检测设备  

E-mail:njxj888@163.com

产品中心

    

     

PRODUCT DISPLAY

新闻中心

当前位置:

Forney 福尼火检探头 IDD-II

Forney 福尼火检探头 IDD-II

Forney 福尼  火焰探测器 HD FLAME DETECTOR


0.00
0.00
  
商品描述

Forney 福尼  火焰探测器 HD FLAME DETECTOR



 Forney 福尼火检探头 IDD-II

通常用于感应重质燃油和煤的火焰。IDD-IU(未过滤)火焰探测器通常用于探测轻质燃油火焰。ID-IL(褐煤)火焰探测器专门设计用于感应褐煤和高灰煤火焰产生的低火焰频率。

IDD-II系列与福尼的支持放大器IDD-9000配合使用。(DR-6101E、RM-IDD和ID-IIA现已过时,取而代之的是IDD9000放大器)。

当感应到火焰时,IDD-II的固态电路会放大硫化铅传感器发出的连续变化的电压信号。信号通过四芯电缆发送到放大器。放大器处理信号并向燃烧器管理系统提供输出。为了无故障运行,探测器电子设备封装在铸钢外壳内。此外,放大器还启动传感器和印刷电路板的定期电子自检,以验证检测器组件的正确操作。

The IDD-II (Filtered) flame detector is typically used for sensing heavy fuel oil and coal flames. The IDD-IIU (Unfiltered) flame detector is typically used forsensing light fuel oil flames. The ID-IL (Lignite) flame detector is specifically designed to sense low flame frequency produced by lignite and high ash coalflames.

The IDD-II Series is used in conjunction with Forney' s supporting amplifier the IDD-9000. (The DR-6101E, RM-IDD and ID-IIA are now obsolete - replacedwith the IDD9000 Amplifiers).

The IDD-II' s solid state circuitry amplifies a continuously changing voltage signal transmitted from the lead sulfide sensor when flame is sensed. The signal isthen sent to the amplifier by way of a four conductor cable. The amplifier processes the signal and provides outputs to the burner management system.

For trouble-free operation, the detector electronics are potted within the cast steel housing. In addition, the amplifier also initiates a periodic, electronicselfcheck of the sensor and printed circuit board to verify proper operation of the detector assembly.

Products and Accessories

IDD-II Infrared DetectorFiltered (#6 Oil & Coal )Part #38321-21
IDD-IIU Infrared DetectorUnfiltered (#2 Oil, #6 Oil & Coal)Part #38321-22
IDD-IIL, Infrared DetectorLignite FuelPart #38321-23
Cooling Chamber (optional)
Part #381071-01

Specifications

Mounting:1” NPT sight pipe fitting
Materials:Cast Steel Housing, Potted Electronics
Electrical:Supplied by Amplifier, 50 VDC and 12 VDC
Electrical Connections:MS Bayonet connector supplied with cable, 1/2” flexible conduit required
Cooling Air Requirements:Front mount applications – minimum cooling air flow of 10 scfm (17 m3/hr) at a
maximum temperature of 120°F (48°C)
Fiber optic applications – minimum cooling air flow of 15 scfm (25 m3/hr) at a
maximum temperature of 120°F (48°C)
Temperature Ratings:32°F to 140°F (0°C to 60°C)
With Cooling Chamber:For ambient temperatures of 140°F to 200°F (60°C to 93°C) the Forney Cooling
Chamber must be used.
Humidity:0-95% relative humidity, non-condensing
Shipping Weight:21 oz
Approvals:Factory Mutual (FM)

‍