The IDD 9000 Flame Amplifier is designed for easy upgrade of existing Forney flame amplifiers with most installations simply requiring a flame amplifier replacement and reconnection of existing wires to improve flame detection and discrimination. The IDD 9000 is available in panel or rack mount; single or dual channel configurations. The dual channel configurations use two fully independent channels to support two flame detectors simultaneously
Compatible Flame Detectors:
IDD-II, Filtered, Infrared Detector Part #38321-21
IDD-IIU, Unfiltered, Infrared Detector Part #38321-22
IDD-IIL, Infrared Detector for Lignite Part #38321-23
UV-4, UV Tube Detector Part #379189-02
IDD 9000 Specifications:
Panel Mount:
Rack Mount:
Dimensions:
10 1/2” x 7 7/8” x 3 7/8” (26.6 cm x 20 cm x 9.8 cm)
6.5 x 14 x 1.75 inches (155.6 x 355.6 x 44.5 mm)
Weight:
5 lbs. 3 oz.
1 lb 7 oz.
Temperature:
32° to 140°F (0° to 60°C)
Humidity:
5% to 95% relative humidity, non-condensing
Power Requirements:
120/240 VAC, 50/60 Hz @ 12 VA
Output Relay Ratings (SPDT):
3 A at 125 VAC, 250 VAC & 30 VDC 3 relays are available for each channel (Lamp, Main Flame & Alarm).